LiYCY (Twisted pair)
Data & Electronic Control Cables / LiYCY (Twisted pair)

LiYCY (TP) / สายคอนโทรนแบบมีชิลล์ คอร์คู่บิดเกลียว
Screened data transmission cable with colour code acc. to DIN 47100 and twisted pairs, LiYCY (TP): Low-frequency PVC data cable, DIN 47100 coded, 0.34² Maxi TERMI-POINT®, Twisted pairs, Flame retardant, Screened, Instrumentation Control
STRUCTURE & SPECIFICATION
| conductor material | bare copper strand |
| conductor class | acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded (7 x 0,25 mm) |
| core material | PVC |
| core identification | acc. to DIN 47100 different colours |
| protection against contact | plastic foil |
| stranding | 2 cores twisted to a pair; pairs stranded in layers |
| shield | copper braid tinned; coverage approx. 85% |
| outer sheath | PVC |
| sheath colour | grey, RAL 7032 |
| rated voltage | 250 V; peak-voltage on 0,14 mm²: 350 V; > 0,14 mm²: 500 V |
| testing voltage | on 0,14 mm² core/core: 2kV; core/shield: 1,2kV > 0,14 mm²: core/core: 2kV; core/shield: 1,5kV |
| conductor resistance | acc. to IEC 60228 cl. 5 |
| insulation resistance | min. 20 MΩ x km |
| current carrying capacity | acc. to DIN VDE, see Technical Guidelines |
| capacity | core/core ca. 120 nF/km; core/shield ca. 160 nF/km |
| min. bending radius fixed | up to 12 mm Ø: 5 x d; up to 20 mm Ø: 7,5 x d; > 20 mm Ø: 10 x d |
| min. bending radius moved | up to 12 mm Ø: 10 x d; up to 20 mm Ø: 15 x d; > 20 mm Ø: 20 x d |
| operat. temp. fixed min/max | -30 °C / +80 °C |
| operat. temp. moved min/max | -5 °C / +70 °C |
| burning behavior | self-extinguishing & flame-retardant acc.to IEC 60332-1 |
| standard | similar to DIN VDE 0812 |