LiHCH
Data & Electronic Control Cables / LiHCH

LiHCH
Screened halogen-free data transmission cable with colour code acc. to DIN 47100, LiHCH: Low-frequency halogen-free data cable flexible (0.34 mm² multi-wire Maxi TERMI-POINT®) DIN 47100, low capacitance, low smoke density, screened
STRUCTURE & SPECIFICATION
| conductor material | bare copper strand |
| conductor class | acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded (7 x 0,25 mm) |
| core material | special halogen-free compound |
| core identification | acc. to DIN 47100 different colours |
| stranding | stranded in layers |
| shield | copper braid tinned, coverage approx. 85% |
| outer sheath | special halogen-free compound |
| sheath colour | grey, RAL 7001 |
| rated voltage | Uo/U: 250 V; peak-voltage on 0,14 mm² 350 V; > 0,14 mm² 500 V |
| testing voltage | on 0,14 mm²: core/core 1,2 kV; core/shield 1 kV > 0,14 mm²: core/core 1,5 kV; core/shield 1 kV |
| conductor resistance | nach IEC 60228 cl. 5 |
| insulation resistance | min. 20 MΩ xkm |
| current carrying capacity | acc. to DIN VDE, s. Techn. Guidelines |
| capacity | core/core ca. 120 nF/km; core/shield ca. 160 nF/km |
| min. bending radius fixed | up to 20 mm Ø 7,5 x d, > 20 mm Ø: 10 x d |
| min. bending radius moved | up to 20 mm Ø 15 x d, > 20 mm Ø 20 x d |
| operat. temp. fixed min/max | -30 °C / +80 °C |
| operat. temp. moved min/max | -5 °C / +70 °C |
| halogen free | acc. to IEC 60754-2 |
| burning behavior | flame-retardant acc. to IEC 60332-3-24 (Cat. C) |
| standard | similar to DIN VDE 0812 |

Call center